Test more than one operating point
A chiller can pass a factory test at one operating condition. That does not show how it will perform at the different loads, water temperatures and operating points it will see during the year. Independent FAT verifies the equipment against the specified requirements before it leaves the factory.
If the chiller is specified for 2 MW of cooling at a stated chilled water flow, return water temperature and entering condenser water temperature, we test it.
If it is specified to turn down to 10 percent load, we test that too.
A factory acceptance test is also one of the last opportunities to identify problems while the equipment is still at the manufacturer. After shipment, the same problem can affect commissioning, project schedules and site costs.
Independent chiller testing before shipment
How the FAT works

References
See our References page for examples of real offshore and industrial projects we have worked on.
Independent chiller verification
We provide independent factory acceptance testing for chillers and chilled water equipment. We verify the equipment against the manufacturer's specifications and the end user's requirements, then report the findings to you. Your customer stays your customer.
Common questions
Verify the chiller before shipment
Get a quote for independent factory acceptance testing of your chiller or chilled water equipment.